Synchronizing Panels are used in industrial and commercial
applications to supply large amounts of loads from paralleling engine generator sets as per load sharing capacity.
Construction
Made of electro-galvanized steel sheets (2.0 mm to 3.0 mm thick for frames and 1.6 mm to 2.0 mm thick for covers).
Coated in Polyester powder coating in RAL 7035.
Enclosure is accessible from front and rear with cable entry from top and bottom with removable gland plates.
Degree of Protection up to IP55
Bus bars
Made of tin plated (ETP) grade copper (Silver plating available upon request). PVC Sleeve is available upon request.
Ratings are designed with current density of 1.5 A/mm². Rated Insulation Voltage is 690V.
Main Bus bars rated up to 10,000A.
Main Bus bar short circuit withstand capacity up to 100kA for 1 Sec.
Neutral and Earth Bus bars are rated at 50 % of the main Bus bar (%100 available upon request)